Eaton
DH1-34038DN-N54C
Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter for HVAC applications - Eaton / Cutler-Hammer (PowerXL DH1) - Rated input voltage (3-phase (3P)) 380Vac-500Vac - Rated output current 38A (Low overload IL) - Rated power 18.5kW (Low overload IL; 400V; 50Hz) / 25HP (Low overload IL; 460V; 60Hz) - Frame size FR3 - IP54 / UL type 12 / NEMA 12 - with BACnet/IP / BACnet MS/TP / Modbus TCP / Modbus RTU communication capability - with conformal coated PCB - with DC choke
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
DH1-34038DN-N54C
Net Price
$5,560.20
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Eaton - PowerXL DH1DH1-34038DN-N54C
Description
Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter for HVAC applications - Eaton / Cutler-Hammer (PowerXL DH1) - Rated input voltage (3-phase (3P)) 380Vac-500Vac - Rated output current 38A (Low overload IL) - Rated power 18.5kW (Low overload IL; 400V; 50Hz) / 25HP (Low overload IL; 460V; 60Hz) - Frame size FR3 - IP54 / UL type 12 / NEMA 12 - with BACnet/IP / BACnet MS/TP / Modbus TCP / Modbus RTU communication capability - with conformal coated PCB - with DC choke
Specifications
Primary brand
Eaton
Secondary brand
Cutler-Hammer
Main function
Variable Speed / Frequency Drive (VSD/VFD) / Inverter
Product series / family name
PowerXL
Sub-range name
DH1
Network frequency
(input) 45-66 Hz
(output) 0-400 Hz
(output) 0-400 Hz
Functions
Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter for HVAC applications
DC choke
DC choke
Supply voltage (AC)
380Vac-500Vac
Type of network
3-phase input (3P)
Rated current
38A (Low overload IL)
Rated active power (kW)
18.5kW (Low overload IL; 400V; 50Hz)
Rated power (HP)
25HP (Low overload IL; 460V; 60Hz)
Protection functions
Overvoltage
Overvoltage trip limit
Undervoltage
Undervoltage trip limit
Earth fault
Input phase supervision
Motor phase supervision
Overcurrent
Unit overtemperature
Motor overload
Motor stall
Motor underload
DC bus overvoltage control
Short-circuit
Surge protection
Overvoltage trip limit
Undervoltage
Undervoltage trip limit
Earth fault
Input phase supervision
Motor phase supervision
Overcurrent
Unit overtemperature
Motor overload
Motor stall
Motor underload
DC bus overvoltage control
Short-circuit
Surge protection
Communication protocol
BACnet/IP
BACnet MS/TP
Modbus TCP
Modbus RTU
BACnet MS/TP
Modbus TCP
Modbus RTU
Operating mode
Frequency control
Speed control
Open-loop speed control
Open-loop torque control
Speed control
Open-loop speed control
Open-loop torque control
Digital inputs
1 x digital input (FWD)
1 x digital input (REV)
1 x digital input (External Fault)
1 x digital input (Fault Reset)
1 x digital input (Preset Speed B)
1 x digital input (Preset Speed B1)
1 x digital input (programmable)
1 x digital input (Force Remote TI+)
1 x digital input (REV)
1 x digital input (External Fault)
1 x digital input (Fault Reset)
1 x digital input (Preset Speed B)
1 x digital input (Preset Speed B1)
1 x digital input (programmable)
1 x digital input (Force Remote TI+)
Digital outputs
1 x digital output (READY)
2 x digital outputs (SPDT Single Pole Double Throw contact type)
1 x digital output (NO contact type)
2 x digital outputs (SPDT Single Pole Double Throw contact type)
1 x digital output (NO contact type)
Analog inputs
2 x analog inputs (4-20mA / 0-10V DC)
Analog outputs
1 x analog output (Output Frequency; 4-20mA)
1 x analog output (Motor Current; 4-20mA)
1 x analog output (Motor Current; 4-20mA)
Degree of protection
IP54
UL type 12
NEMA 12
UL type 12
NEMA 12
Ambient air temperature for operation
-10...+40 °C
Ambient air temperature for storage
-40...+70 °C
Chemical resistance
conformal coated PCB
Application type
General-purpose HVAC drive
Manufacturer product status
Commercialized
Compliant with standard(s)
IEC 61800-5-1
EN 61800-5-1
IEC 61800-5-2
EN 61800-5-2
UL 508C
IEC 61508
EN 62061
EN ISO 13849-1
IEC 61800-3
EN 61800-3
UL
cUL
CE
C-Tick
RoHS
Plenum rated
EN 61800-5-1
IEC 61800-5-2
EN 61800-5-2
UL 508C
IEC 61508
EN 62061
EN ISO 13849-1
IEC 61800-3
EN 61800-3
UL
cUL
CE
C-Tick
RoHS
Plenum rated
Degree of pollution
2
Related Documents
Name | Last Update | Language |
---|---|---|
Eaton - PowerXL M-Max SVX H-Max SPX EGF CFX HCX CPX RGX LCX SPA SPN SPI - Catalogue.pdf | 23 Jun 2020 | English (US) |