Eaton
NGH412032E
Molded/Moulded Case Circuit Breaker (MCCB) - Eaton (Series G) - NG-Frame) - 4 poles (4P3d) - Rated current (In) 1200A at +40°C - Switching capacity / short circuit rating SCCR 35kA (600Vac) - Electronic trip unit - Digitrip RMS 310+ (LSI) trip unit - Imperial tapped line/load conductor terminals
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
NGH412032E
Net Price
$58,388.44
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Eaton Cutler-Hammer - Series G
Description
Molded/Moulded Case Circuit Breaker (MCCB) - Eaton (Series G) - NG-Frame) - 4 poles (4P3d) - Rated current (In) 1200A at +40°C - Switching capacity / short circuit rating SCCR 35kA (600Vac) - Electronic trip unit - Digitrip RMS 310+ (LSI) trip unit - Imperial tapped line/load conductor terminals
Specifications
Primary brand
Eaton
Secondary brand
Cutler-Hammer
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Series G
Sub-range name
NG-Frame
Network frequency
50/60 Hz
Functions
Molded/Moulded Case Circuit Breaker (MCCB)
Rated current
1200A
Frame current rating
630 AF
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
850 V
Connection type
Imperial tapped line/load conductor
Poles
4 Pole(s)
Protected poles
3 Pole(s)
Short circuit breaking rating
100kA (240Vac)
65kA (480Vac)
35kA (600Vac)
65kA (480Vac)
35kA (600Vac)
Ultimate short circuit current breaking capacity (Icu)
100kA (240Vac)
70kA (415Vac)
25kA (690Vac)
70kA (415Vac)
25kA (690Vac)
Service short circuit current breaking capacity (Ics)
50kA (415Vac)
13kA (690Vac)
13kA (690Vac)
Trip unit type
Electronic
Digitrip RMS 310+ (LSI)
Digitrip RMS 310+ (LSI)
Protection functions
L (Long-time protection)
S (Short-time protection with fixed time delay)
I (Instantaneous protection)
S (Short-time protection with fixed time delay)
I (Instantaneous protection)
Ambient air temperature for operation
+40 °C
Electrical durability (with load)
3 000 operations
Service short circuit current breaking capacity (Ics)
100kA (240Vac) kA
Manufacturer product status
Commercialized
Rated voltage (AC)
(NEMA) 600 V
(IEC) 690 V
(IEC) 690 V
Related Documents
Name | Last Update | Language |
---|---|---|
Eaton - Cutler-Hammer - MCCBs - Catalog.pdf | 06 Aug 2018 | English (US) |
Eaton - Cutler-Hammer - MPCBs - Leaflet.pdf | 06 Aug 2018 | English (US) |